Toxic & Flammable Gas Reference Data – OSHA, NIOSH

Engineering reference for industrial gas detection and safety system design, with TWA, STEL, LEL limits, relative density.

Why This Reference Matters

This page provides indicative engineering reference data commonly used during:

  • Gas detector selection, measuring range, threshold design and layout
  • Preliminary hazard analysis (HAZID / HAZOP)
  • Compliance review and system sizing
  • Concept and FEED stage documentation

Values shown are typical industry references compiled from OSHA, NIOSH, ACGIH and manufacturer technical literature. Final project decisions must follow site-specific risk assessment, design criteria, application requirement and applicable standards.


Installation Height Logic (important):

  • Lighter than air (<1.0): Install detectors near ceiling
  • Heavier than air (>1.0): Install detectors near floor
  • Near air density (~1.0): Install at breathing zone (1.2–1.5 m)
GasLEL (% vol)UEL (% vol) Density (Air=1)Detector LocationAction
Methane (CH₄) 5 15 0.55 Near ceiling Calculate
Hydrogen (H₂) 4 75 0.07 Near ceiling Calculate
LPG (Propane / Butane) 2.1 9.5 1.8 Near floor Calculate
CNG / PNG 5 15 0.55 Near ceiling Calculate
Hydrogen Sulfide (H₂S)
(Also toxic)
4.3 45.5 1.19 Near floor Calculate
Ammonia (NH₃)
(Also toxic)
15 28 0.6 Near ceiling Calculate
Formaldehyde
(Also toxic)
7 73 1.07 Breathing zone Calculate
Hydrogen Cyanide (HCN)
(Also toxic)
5.6 40 0.94 Breathing zone Calculate
Phosphine
(Also toxic)
1.8 98 1.2 Breathing zone Calculate
Acetone
(Also toxic)
2.6 12.8 2 Near floor Calculate
IPA (Isopropyl Alcohol)
(Also toxic)
2 12 2.1 Near floor Calculate
Toluene
(Also toxic)
1.2 7.1 3.1 Near floor Calculate
Hexane
(Also toxic)
1.2 7.5 3 Near floor Calculate
Petrol Vapour 1.4 7.6 3 Near floor Calculate
Diesel Vapour 0.6 7.5 4 Near floor Calculate
VOC / Solvent Vapour (Generic)
(Also toxic)
1–3 6–12 >1 Near floor Calculate
Styrene
(Also toxic)
1.1 6.1 3.6 Near floor Calculate
GasTWASTELIDLH DensityDetector LocationAction
Carbon Monoxide (CO) 25 200 1200 0.97 Breathing zone Calculate
Carbon Dioxide (CO₂) 5000 30000 40000 1.53 Breathing zone Calculate
Oxygen (O₂) 19.5–23.5 % 1.11 Breathing zone Calculate
Nitrogen (N₂) 0.97 Ceiling (deficiency) Calculate
Nitrous Oxide (N₂O) 25 1.53 Breathing zone Calculate
Hydrogen Sulfide (H₂S)
(Also flammable)
10 15 100 1.19 Near floor Calculate
Ammonia (NH₃)
(Also flammable)
25 35 300 0.6 Near ceiling Calculate
Formaldehyde
(Also flammable)
0.75 2 20 1.07 Breathing zone Calculate
Hydrogen Cyanide (HCN)
(Also flammable)
10 50 0.94 Breathing zone Calculate
Phosphine
(Also flammable)
0.3 1 50 1.2 Breathing zone Calculate
Acetone
(Also flammable)
2 Near floor Calculate
IPA (Isopropyl Alcohol)
(Also flammable)
2.1 Near floor Calculate
Toluene
(Also flammable)
3.1 Near floor Calculate
Hexane
(Also flammable)
3 Near floor Calculate
VOC / Solvent Vapour (Generic)
(Also flammable)
>1 Near floor Calculate
Chlorine (Cl₂) 0.5 1 10 2.5 Near floor Calculate
Ozone (O₃) 0.1 0.3 5 1.6 Breathing zone Calculate
Sulfur Dioxide (SO₂) 2 5 100 2.26 Near floor Calculate
Nitrogen Dioxide (NO₂) 3 5 20 1.6 Breathing zone Calculate
Nitric Oxide (NO) 25 100 1.04 Breathing zone Calculate
Phosgene 0.1 2 3.4 Near floor Calculate
Hydrofluoric Acid (HF) 3 6 30 0.92 Breathing zone Calculate
Hydrochloric Acid (HCl) 5 50 1.3 Breathing zone Calculate
Styrene
(Also flammable)
3.6 Near floor Calculate

×


ppm:

% Volume:

% LEL:

Online Gas Concentration Conversion Calculator

PPM ↔ % Volume Converter

ppm:

% Volume:

1% volume = 10,000 ppm

Gas Concentration ↔ %LEL Converter

ppm:

% Volume:

% LEL:

%LEL is referenced to gas-specific Lower Explosive Limit (% volume).

Applicable only for flammable gases. LEL values are gas-specific.

Common Engineering Mistakes

  • Using ppm alarms for flammable gases instead of %LEL
  • Installing detectors at wrong height due to ignoring gas density
  • Mixing OSHA TWA with ACGIH STEL incorrectly
  • Using laboratory limits for outdoor or ventilated areas
  • Ignoring response time and cross-sensitivity during selection
  • Improper low voltage earthing, leading to static charges accumulation
  • Improper cable selection and installation

APPLICATION SECTORS

This reference is typically used in:

  • Oil & Gas production & processing
  • Refineries & petrochemical plants
  • Chemical manufacturing units
  • Fertilizer & ammonia plants
  • Warehouses & cold storage
  • Battery energy storage systems (BESS)
  • Wastewater & utility plants
  • LNG / LPG facilities

STANDARDS & GUIDELINES (REFERENCE)

  • OSHA Occupational Exposure Limits
  • NIOSH IDLH Guidelines
  • ACGIH TLV recommendations
  • IEC / EN gas detection standards
  • NFPA flammable gas practices
  • ATEX / IECEx installation principles

Technical Disclaimer

Data provided is for engineering reference only. Final gas detection design, alarm limits, installation height and compliance shall be confirmed through project-specific risk assessment, applicable codes and authority requirements.